iUnigear Air Insulated Switchgear

Air Insulated Switchgear

UN-Panel Air Insulated Switchgear

medium voltage switchgear

for 12-17,5 and 24kV

Product Description

Air Insulated Switchgear

medium voltage switchgear

ZS1 is medium voltage switchgear with a metal enclosure, suitable for indoor installations. Metal clad and seperate the compartments from each other’s. Their live parts are air-insulated. Since the switchgear is highly modular type, this make simple selection of components required by any application. The functional units of the switchgear are guaranteed arc proof in accordance with the IEC 62271-200 Standards. All the installation, operation and maintenance operations can be carried out from the front of the switchgear. The vacuum circuit breaker and earthing switches are operated from the front with the door closed. The switchgear can be back to wall installed.

 

Protection Components

The range of apparatus available for ZS1 switchgear is the most complete on the market, including:

  • Withdrawable vacuum or gas VCB
  • withdrawable vacuum contactor

This makes it possible to offer a single switchgear-user interface, with the same operational and maintenance procedures.

The switchgear can be fitted with instrument transformers or sensors for current and voltage measurement and protection and any brand circuit breakers or relay protection.

 

Switchgear, busbar configuration

In the completion of the traditional functional units in single busbar arrangement, the ZS1 switchgear platform is fitted with:

  • Double busbar
  • Compact units equipped with vacuum contactors & fuses,
  • Double Busbar Systems.

Working conditions

Ambient conditions:

  • – 5 °C to + 40 °C

For different temperature ranges, Unisun provide heater or cooling fan with temperature monitor as solution

Ambient humidity:

  • up to 95% RH average in 24h
  • up to 90% RH average in monthly
  • water vapour pressure up to 2.2 kPa in 24h
  • water vapour pressure up to 1.8 kPa monthly
  • The normal working altitude is up to 2,000 m above sea level. For higher altitude applications, please consult upon ordering
  • Install in normal, non-corrosive and uncontaminated environment

 

Standards

Unisun ZS1 switchgear and main components comply with the following Standards:

  • IEC 62271-1 for general purposes.
  • IEC 62271-200 for the switchgear.
  • IEC 62271-102 for the earthing switch.
  • IEC 62271-100 for the circuit-breakers.
  • IEC 60071-2 for the insulation coordination.
  • IEC 62271-106 for the contactors.
  • IEC 60265-1 for the switch-disconnectors.
  • IEC 60529 for degree of protections.

 

Colour of the external surfaces

RAL7035 – ligh grey (front doors and side cover). Other colours are available on request.

 

Degrees of protection

The degrees of protection of the switchgear conform with IEC 60529 Standards.

UN-Panel ZS1 switchgear is normally supplied with the following standard degrees of protection:

  • IP4X for the enclosure.
  • IP2X for the partition between compartments.

higher degree of protection could be customized pls contact Unisun technical dept.

 

Air Insulated Switchgear Electrical Parameter

Rated voltage kV 7.2 12 17.5 24
Rated insulation voltage kV 7.2 12 17.5 24
Rated power frequency withstand voltage kV 1min 20 28 38 50
Rated lightning impulse withstand voltage kV 60 75 95 125
Rated frequency Hz 50/60 50/60 50/60 50/60
Rated short time withstand current kA 3  s …50 …50 …50 …31.5
Peak current kA …125 …125 …125 …80
Internal arc withstand current kA 1 s …50 …50 …50 …31.5
Main busbar rated current A …4,000 …4,000 …4,000 …3,150
Circuit-breaker rated current A 630 630 630 630
1,250 1,250 1,250 1,250
1,600 1,600 1,600 1,600
2,000 2,000 2,000 2,000
2,500 2,500 2,500 2,300
3,150 3,150 3,150 2,500

Send your message to me